Tuesday, March 31, 2009

New TJI'S

New TJI'S (holes for trades)

Wind Borne Debris Information

From: Spence Castello
Sent: Thursday, January 22, 2009 4:04 PM
To: Tod Burns; Steve Szymanski; Bill Newns; Jason Corbell
Subject: FW: Wind Borne Debris Region

-----Original Message-----
From: David Conner [mailto:DConner@ncdoi.net]
Sent: Thursday, January 22, 2009 3:47 PM
To: Spence Castello
Cc: Timothy Morrison; Bob Speed; Bill Moeller; Mark Bailey; Mike Page; Alan Greene; Joe Sadler; Barry Gupton
Subject: Wind Borne Debris Region

Mr. Castello

It is the purpose of this writing to follow up our phone conversations of 1/22/09 and 1/23/09 regarding those areas encompassed by the 2009 code definition of Wind Borne Debris Region. The definition reads; “Areas within hurricane prone regions defined as that area east of the inland waterway from the NC/SC state line north to Beaufort Inlet and from that point to include the barrier islands to the NC/VA state line.”

The definition is intended to address two coastal groups independently as follows:

1. From the NC/SC state line north to Beaufort Inlet – The wind borne debris region is that area east of the inland waterway (intracoastal waterway)

2. From Beaufort Inlet north to the NV/VA state line – The wind borne debris region is the barrier islands


I hope this information helps.

David W. Conner, Sr., P.E.

Building Code Consultant

Office of State Fire Marshall

NC Department of Insurance

Phone (919) 661-5880 Ext. 229

FAX (919) 662-4414

Use of SEC Aluminum Wire in Dwelling (also applies to SEC Copper Conductors)

From: Ron Chilton [rchilton@ncdoi.net]
Sent: Friday, December 12, 2008 9:55 AM
To: Bill Newns
Subject: RE: SEC 334.80

Hi Bill,
I don’t think I answered this question yet, I apologize.

If Table 310.15(B)(6) applies to a main power feeder, there is no temperature limitation mentioned in that Table. There must not be but one feeder that supplies the entire load of the dwelling in order to use that Table. Note that 4/0 AL conductor, with an allowable ampacity per Table 310.15(B)(6) of 200 amps, is only rated at 150 amperes in Table 310.16, at 60-degrees. The diversity built into the calculation is the reasoning behind this Table allowing to seemingly overload the conductors. If a Meter-Main combo is used with feed-through lugs, no circuits may be fed from that outside panel to the dwelling and still use Table 310.15(B)(6).

If the feeder is not the main power feeder, then Table 310.16 must be used and the 60-degree ampacity must be adhered to.

Hope this helps, if further assistance is needed, please contact me.
Thanks,

Ron
--------------------------------------------------------------------------------

From: Bill Newns [mailto:bnewns@co.currituck.nc.us]
Sent: Wednesday, December 10, 2008 3:55 PM
To: Ron Chilton
Subject: SEC 334.80

Ron,

I have a house with a meter with a service disconnect outside with SER cable running from the disconnect to the inside panel box, does article 334.80 apply to the wire from the disconnect to the sub panel box inside the house for derating to 60 degree?

Thanks

Bill Newns

Friday, March 27, 2009

Night Club Fire in R.I. Why Egress is so important

Sunrooms

When constructing a sunroom or turning a screened porch/deck into a sunroom, the NEC requires outlets be installed per wall space requirements and a switched lighting outlet to be installed in the sunroom and at exterior entrances of sunroom, per 2008NEC 210.50(A) and 210.70(2)(b)

Also decks, porches and balcolnies great than 20 sq. ft. require a GFIC weather resistant outlet on them. 2008 NEC 210.52(E)(3)

Thursday, March 26, 2009

Welcome

Welcome to the Currituck County Inspections blog, hopefully this will be a way to communicate better with our customers.

Thank you!